Previously when a drive faulted, the statechange-led.sh script would lookup
the drive's LED sysfs entry in /sys/block/sd*/device/enclosure_device, and
turn it on. During testing we noticed that if you pulled out a drive, or if
the drive was so badly broken that it no longer appeared to Linux, that the
/sys/block/sd* path would be removed, and the script could not lookup the
LED entry.
To fix this, this patch looks up the disks's more persistent
"/sys/class/enclosure/X:X:X:X/Slot N" LED sysfs path at pool import. It then
passes that path to the statechange-led script to use, rather than having the
script look it up on the fly. This allows the script to turn on/off the slot
LEDs even when the drive is missing.
Closes#5309Closes#2375
1. Enable multipath autoreplace support for FMA.
This extends FMA autoreplace to work with multipath disks. This
requires libdevmapper to be installed at build time.
2. Turn on/off fault LEDs when VDEVs become degraded/faulted/online
Set ZED_USE_ENCLOSURE_LEDS=1 in zed.rc to have ZED turn on/off the enclosure
LED for a drive when a drive becomes FAULTED/DEGRADED. Your enclosure must
be supported by the Linux SES driver for this to work. The enclosure LED
scripts work for multipath devices as well. The scripts will clear the LED
when the fault is cleared.
3. Rate limit ZIO delay and checksum events so as not to flood ZED
ZIO delay and checksum events are rate limited to 5/sec in the zfs module.
Reviewed-by: Richard Laager <rlaager@wiktel.com>
Reviewed by: Don Brady <don.brady@intel.com>
Reviewed-by: Brian Behlendorf <behlendorf1@llnl.gov>
Signed-off-by: Tony Hutter <hutter2@llnl.gov>
Closes#2449Closes#3017Closes#5159